Back to photostream

6kV/560-6600kw General Medium Voltage Drive

www.hiconics-global.com/products/6kv-560-6600kw-general-m...

Hiconics's medium voltage drive has new cabinet type and power-cell structure and smaller volume. The power unit and transformer are arranged in front and back, with compact structure. Through thermal analysis design, on-site installation costs and infrastructure costs can both be reduced on the basis of ensuring heat dissipation.

Technical Parameters of 6kV/560~6600kW General Medium Voltage Drive

VoltageMotor Power(KW)Output Capacity(KVA)ModelWeight

(kg)Dimension

(W*H*D)Cabinet Type

 

6kV250315HIVERT-Y/T 06/03126502150×1400×2400

2150×1400×2400

2815×1400×2400

2150×1400×2400

2150×1400×2400

2815×1400×2400LA1.1

LA1.1P

LA1.1Q

LC1.1

LC1.1P

LC1.1Q

315400HIVERT-Y/T 06/0402760

400500HIVERT-Y/T 06/0482930

450560HIVERT-Y/T 06/0553160

500630HIVERT-Y/T 06/0613360

560700HIVERT- Y/T 06/06839853450×1600×2250

3450×1600×2250

4115×1600×2250

3450×1600×2250

3450×1600×2250

4115×1600×2250LA2.1

LA2.1P

LA2.1Q

LC2.1

LC2.1P

LC2.1Q

630800HIVERT- Y/T 06/0774042

710890HIVERT- Y/T 06/0864160

8001000HIVERT- Y/T 06/0964382

9001150HIVERT- Y/T 06/1094590

10001250HIVERT- Y/T 06/1304792

11201400HIVERT-Y/T 06/1354985

12501600HIVERT-Y/T 06/1545285

12501600HIVERT- Y/T 06 /154P59304150×1600×2250

4150×1600×2250

4815×1600×2250

4150×1600×2250

4150×1600×2250

4815×1600×2250LA3.1

LA3.1P

LA3.1Q

LC3.1

LC3.1P

LC3.1Q

 

Specification of 6kV/560-6600kw General Medium Voltage Drive

ItemParameters

VFD rated power210~28000kVA※

Rated voltage3.3kV~11kV(-20%~+5%)※(Out of range, special instructions required)

Rated Frequency50Hz/60Hz(-10%~+10%)※

Control Power380VAC, 30kVA

Rated input power factor≥0.96

Effciency>96%

Output frequency range0~80Hz※

Speed accuracy±0.5%(Open loop vector) ±0.1%(close loop vector)

Instantaneous over-current protection150%( Can be customized according to user requirements)

Over capacity120% load for 120s

Torque limitation10%~150%

Analog input3 ways 4~20mA/Excitation feedback 4~20mA(Customized)

Analog output4ways 4~20mA

Host communicationIsolated RS485 interface, ModBus RTU, Profibus DP(optional), Industry Ethernet

Acceleration and deceleration time5s~6000s ( related to load)

DI14 inputs/22 outputs (Output 8 ways can be defined)

Environment temperature-5~+45℃※

Storage/transportation temperature-25~+55℃※

Cooling methordAir forced cooling (AF) / Water cooled (WF)/Air forced water cooled (AFWF)

Humidity<95%, no condensation

Altitude≤1000m, when altitude is higher than 1000m, each 100 meter increasing needs 1%

derating of VFD

DustNon-conductive, no causticity, <6.5mg/dm3※

Protection levelIP30※

Cabinet colorsRAL 7032(customized)